1、Part No. 17357 Rev. 5 Date 9/26/00 POWER MULTIMETER OPERATING AND INSTRUCTION MANUAL CAT. NO. PMM-1 It is essential that this instruction book be read thoroughly before putting the equipment in service! RadioFans.CN 收音机爱 好者资料库 REVISIONS HISTORY RevisionECN#Date 004/28/97 12756206/27/97 22804012/01/9
2、8 32851006/17/99 411/29/99 5288349/20/00 IMPORTANT The information and data contained within this instruction manual are proprietary with AVO International. The equipment described herein may be protected by one or more U.S. letters patent. AVO International specifically reserves to itself all right
3、s to such proprietary information as well as all rights under any such patent, none of which is waived by the submission of this instruction manual to anyone. The recipient, if a Government agency, acknowledges that this instruction book and the equipment described were procured with Limited Rights
4、to technical data as described in ASPR 9-203 (b). Copyright AVO International 1997, 1998, 1999, 2000 RadioFans.CN 收音机爱 好者资料库 i TABLE OF CONTENTS 1OPERATOR SAFETY. 1 1.1DESCRIPTION . 1 1.2EXPLANATION OF SAFETY SYMBOLS. 1 1.3GROUNDING. 2 1.4POWER CORD AND FUSES. 2 2GENERAL INFORMATION . 3 2.1DESCRIPTI
5、ON . 3 2.2APPLICATIONS. 3 2.3FEATURES.3 2.4ELECTRICAL SPECIFICATIONS. 5 2.5MECHANICAL AND ENVIRONMENTAL SPECIFICATIONS. 6 2.6ORDERING INFORMATION. 6 2.7CHANGES. 7 2.8WARRANTY. 7 3INSTALLATION. 9 3.1UNPACKING AND INSPECTION. 9 3.2PREPARATION FOR USE . 9 3.3REPACKING AND SHIPMENT. 9 4OPERATING INSTRUC
6、TIONS. 10 4.1PANEL CONTROLS AND OPERATING FUNCTIONS. 10 4.2SAFETY CONSIDERATIONS. 12 4.3USING THE INTERNAL BATTERY. 12 4.4GENERAL OPERATING INSTRUCTIONS. 14 4.5SINGLE PHASE OPERATION . 14 4.5.1SELECTING THE INPUT CHANNEL. 15 4.5.2THE MEASURING FUNCTIONS. 17 RadioFans.CN 收音机爱 好者资料库 ii 4.6THREE-PHASE
7、OPERATION . 18 4.6.1SELECTING THE CONFIGURATION . 18 4.6.2THE MEASURING FUNCTIONS. 20 4.7CLAMP-ON CURRENT AND POTENTIAL TRANSFORMER OPERATION . 21 4.7.1MEASURING PRIMARY CURRENT. 22 4.7.2VERIFYING THE RATIOS OF CTS. 23 4.8HIGH-SPEED SINGLE-PHASE CAPTURE MODE . 24 4.8.1THE MEASURING FUNCTIONS. 25 4.9
8、TIMER/RELAY OPERATION. 28 4.9.1MODES OF OPERATION. 28 4.9.2THE MEASURING FUNCTIONS. 29 4.10 VIEW SAVED DATA Directory. 30 4.11 TIMED DATA TRANSMISSION. 31 4.12 SETTING THE CLOCK AND DATE. 35 4.13 PERIPHERAL OPERATION. 35 4.13.1 PRINTER PORT. 35 TABLE 4-1DOT MATRIX PRINTER PORT PIN-OUT . 36 4.13.2 RS
9、232 SERIAL DATA PORT. 36 TABLE 4-2 RS232 CONNECTOR PIN-OUT . 37 POWER MULTIMETER COMMAND SET. 38 CALIBRATION PROCEDURES. 43 PMM-1 QUICK TIPS. 46 EXAMPLES .48 EXCEL PROGRAM INSTRUCTIONS. 56 5SERVICE AND MAINTENANCE . 63 1 1OPERATOR SAFETY ATTENTION: READ THIS MANUAL BEFORE PROCEEDING WITH INSTALLATIO
10、N AND OPERATING THE INSTRUMENT. 1.1DESCRIPTION This instrument must be operated, used and serviced ONLY by trained, qualified personnel. Misuse of electrical instruments can result in personal injury and damage to the apparatus under test. Obey all applicable safety rules and regulations at all time
11、s. Refer to the following sections of this manual for operating specifications and procedures. 1.2EXPLANATION OF SAFETY SYMBOLS AVO International uses, where applicable, the following IEC 417 symbols on its instruments: This symbol indicates that the operator of the instrument must refer to the inst
12、ruction manual for further explanation and clarification. ? ? ? ? ? Safety Ground Terminal. This terminal must be connected to an earth ground before making other connections to the instrument and prior to operating it! This red symbol indicates that high voltage (i.e., any voltage equal or greater
13、than 1000 Volts) is present on the terminal. Use extreme care. This is the symbol for a sinusoidal AC voltage or current. AC or DC voltage. 2 1.3GROUNDING Where a ground binding post or a grounding lead is provided on the instrument, it must be connected to an earth ground PRIOR to making any other
14、connections. WARNING: To avoid electric shock do not interrupt the connection to the protective safety ground. 1.4POWER CORD AND FUSES The power cord must be connected to a grounded supply system with proper electrical ratings, as indicated on the instrument. In the case of detachable power cords, o
15、nly the cord supplied or specified by AVO International should be used. WARNING: TO AVOID ELECTRIC SHOCK ALWAYS DISCONNECT THE POWER CORD FROM THE SUPPLY CIRCUIT BEFORE SERVICING THE INSTRUMENT OR WHEN REPLACING A FUSE. WARNING: ALL FUSES MUST BE REPLACED WITH THE SAME TYPE AND CURRENT AND VOLTAGE R
16、ATINGS. SHORT-CIRCUITING THE FUSEHOLDER IS PROHIBITED. 3 2GENERAL INFORMATION 2.1DESCRIPTION The AVO International POWER MULTIMETER (Model PMM-1) is a next generation portable battery/line operated multifunction instrument for measuring AC or DC voltage, AC primary and secondary current, power, reac
17、tive power, phase angle and frequency of a single or three phase electrical system. POWER MULTIMETER is easily configured to measure the amplitude and phase angle between any two voltage and current inputs. All measured quantities are displayed simultaneously on an easy-to-read graphic display. The
18、unique firmware in the POWER MULTIMETER, combined with a built-in microprocessor-based timer, is specifically designed to ease testing and commissioning of protective relay systems, including induction unit pick-up and timing tests. The internal timer responds to a variety of start and stop gates, i
19、ncluding the application of AC or DC voltage, and opening or closing of dry contacts. POWER MULTIMETER is a menu driven instrument equipped with data- retention and TIMED data-logging capabilities. Automatically stores measured data at user defined intervals. Transmit them to a PC on a pre-programme
20、d time interval or save data directly to NOV RAM memory. Other important features include accurate phase angle measurement at very low current levels and the high speed measurement mode. 2.2APPLICATIONS POWER MULTIMETER is an ideal instrument for use in general electrical systems maintenance, in ele
21、ctrical machine repairs, in protective relay testing, or in monitoring power at the electrical service entrance. In the protective relay application area, POWER MULTIMETER is designed to perform fast, accurate checking and testing of protective relay and meter installations, during their commissioni
22、ng and in routine maintenance. Also, combined with a source of voltage and/or current, POWER MULTIMETER becomes an excellent tool for testing and calibrating various types of protective relays. 2.3FEATURES Battery and line operated, with an automatic built-in charger. Rugged, ergonomic and light pla
23、stic enclosure. 4 3 independent voltage and current channels, with a built-in timer. Specifically designed to ease testing and commissioning of protective relay systems. Simultaneously measures and displays voltage, current, phase angle, power, reactive power, power factor, and frequency of single o
24、r three phase systems. Wide current and voltage operating ranges. High speed measurement mode, with up to 1200 sets of readings in single phase mode and up to 400 sets of readings in three phase mode. Accurate phase angle measurement at very low current levels. Timer mode, phase angle between the vo
25、ltage and current is measured and displayed. Auto-ranging to reduce test time, with manual over-ride. RS232 data and parallel printer output ports. Large, easy-to-read, high-resolution LCD display. Menu driven, easy to operate. Data storage for saving measured values. Programmable Time Data Logging
26、to Memory. Customize C.T. ratio inputs up to a ratio of 9999:1 or 9999:5. Customize P.T. ratio inputs up to a ratio of 9999:1 or 9999:5. Microsoft EXCEL workbook to obtain data. Harmonic measurement of any selected voltage or current up to the 49th harmonic. 5 2.4ELECTRICAL SPECIFICATIONS SPECIFICAT
27、IONS Input:Line: 90-253 V, 50/60 Hz, 30 VA Battery: Internal, sealed lead-acid, rechargeable battery with an internal automatic charger. Safety features include Internal battery over-charging and charge exhaustion protection. Operation Time: 10-Hour continuous on full charge. Voltage: 0 - 650 Volts
28、(AC/DC) in 8 ranges, with 0.1% resolution. Accuracy at 50/60 Hz: 0.05% of reading, from 3-650 AC Volts. (21 - 25C) 0.1% of reading, from 3-650 AC Volts. (0 - 50C) 0.1% of reading, from 3-650 DC Volts. Input impedance: 1 M. Max input: 1000 Volts, from inputs to the chassis or between inputs. Current:
29、 0 - 100 Amperes (AC) in 10 ranges, with 0.1% resolution. Accuracy at 50/60 Hz: 0.05% of reading, from 0.10-10 Amperes (21 - 25C). 0.1% of reading 10 amperes. Burden at 5A: 0.1VA. Phase Angle: 0 - 180.0 and 0 - 360 lead or lag, with 0.01 resolution. Accuracy at 50/60 Hz: 0.05 for input levels above
30、30 Volts and 1 Amps, 0.5 for input levels above 3 Volts and 0.02 Amps 2 input levels below 3 Volts and 0.02 Amps. Power: 0 - 100 KW, with 0.1% resolution. Highest resolution is 0.001 Watt. Accuracy at 50/60 Hz: 0.1% of VA. Reactive Power: 0 - 100 KVAR with 0.1% resolution. Highest resolution is 0.00
31、1 VAR Accuracy at 50/60 Hz: 0.1% of VA. Operating Frequency: 45 - 65 Hz, with 0.01 Hz resolution. Accuracy: 0.03 Hz. Time:. 0.000 to 999.999 Seconds. Accuracy: 0.001 Seconds Start/Stop Inputs: 5 - 300 Volts AC, DC, or dry contacts closure or opening. Input resistance: 1000 Minimum. Response Time: Re
32、gular single-phase mode: 1 reading per second High Speed Mode: 20 readings per second/60 seconds max. Three-phase mode: 1 set of readings every second. Specifications subject to change. 6 2.5MECHANICAL AND ENVIRONMENTAL SPECIFICATIONS Case Material: Dimensions:344W x 242H x 242D millimetres (13.5W x
33、 9H x 9D inches) Weight:6.0 Kg (13.4 Lbs), approximately Operating Temperature:-15C to 55C (5F to 131F) Storage Temperature:-30C to 75C (-22F to 167F) Relative Humidity:10 to 95%, NON-CONDENSING 2.6ORDERING INFORMATION Cat. No. POWER MULTIMETERPMM-1-V2 The instrument is shipped complete with: Line c
34、ord, three wire, 120V6828 Instruction Manual17357 (2) Fuses 1.0 A 250 V, 5 x 20 mmMC7797 Accessory Pouch External Mount Portable Case17355 PMM1-V2.xls software51768 The following optional accessories are available: Standard Potential Leads set of 4, 2m 835312 Fused Potential Leads set of 4, 2m830213
35、 20-Amps Current Leads, States Plugs set of 3, 1m 835313 20-Amp Current Leads, clips set of 3, 1m 835314 100-Amp Current Leads set of 3, 1m 835315 1000:1 Clamp-On Current Transformer 830312 1000:5 Clamp-On Current Transformer 835318 3000:1 Clamp-On Current Transformer 835319 3000:5 Clamp-On Current Transformer 835320 200:1 Minature Clamp-On