1、 AVTMTTR25 Rev. C April 2008 Instruction Manual AVTMTTR25 for TTR25 Handheld TTR Transformer Turn Ratio Test Set Catalog No. TTR25 High-Voltage Equipment Read the entire manual before operating. Aparato de Alto Voltaje Antes de operar este producto lea este manual enteramente. M 2621 Van Buren Ave N
2、orristown, PA 19403-2329 610-676-8500 RadioFans.CN 收音机爱 好者资料库 RadioFans.CN 收音机爱 好者资料库 TTR25 Handheld TTR Transformer Turn Ratio Test Set Instruction Manual RadioFans.CN 收音机爱 好者资料库 Copyright Notice Copyright 2005 by Megger. All rights reserved. Disclaimer Notice The information contained in this manu
3、al is believed to be adequate for the intended use of the product. If the product or its individual instrument are used for purposes other than those specified herein, confirmation of their validity and suitability must be obtained from Megger. Refer to the warranty information included at the end o
4、f this instruction manual. Specifications are subject to change without notice. WARRANTY Products supplied by Megger are warranted against defects in material and workmanship for a period of one year following shipment. Our liability is specifically limited to replacing or repairing, at our option,
5、defective equipment. Equipment returned to the factory must be shipped prepaid and insured. This warranty does not include batteries, lamps, or other expendable items, where the original manufacturers warranty shall apply. We make no other warranty. The warranty is void in the event of abuse (failur
6、e to follow recommended operating procedures) or failure by the customer to perform specific maintenance as indicated in this manual. AVTMTTR25 Rev C April 2008 i TABLE OF CONTENTS 1 INTRODUCTION. 1 About the TTR25.1 Electrical Theory and Practice .2 Applications for the TTR25 .4 Upon Receipt of the
7、 TTR25 .5 Safety First.5 How to Use This Manual.5 2 SAFETY. 7 Overview.7 Safety Requirements .7 Cautions and Warnings.8 3 CONTROLS and the X terminals on the test lead set must be connected to the H terminals on the CT. NOTE: Dots on the housing of the transformer are commonly used to identify termi
8、nals of the same polarity. F WARNING Failure to observe proper connections will result in a safety hazard and may result in damage to the test set or CT. Failure to observe voltage rating of low-current X winding may result in damage to the CT. NOTES: 1. The TTR25 may supply up to 100 mA of excitati
9、on current. The TTR25 will automatically select the appropriate test voltage (8 V, 1.5 V, or 0.5 V) when testing CTs. Some current transformers with turn ratio of 50:5 and less may require more than 100 mA of excitation current when excited from 0.5 V source. These CTs can not be tested with the TTR
10、25. 2. Expect that polarity of the windings is normal (“+” sign is displayed in front of the turns ratio test result). Unmounted CTs NOTE: The illustrated connection diagrams are provided as connection guides and do not suggest the physical location of the bushings / terminals of the device being te
11、sted. Figure 4-8 shows the setup for testing unmounted current transformers. Figure 4-9 shows the setup for testing the taps on a multiple-tap CT. M AVTMTTR25 Rev C April 2008 18 Figure 4-8 Setup for Testing Unmounted Current Transformer Figure 4-9 Setup for Testing Taps on Multiple Tap CT TTR 25 Se
12、tup, Connections 9-pin D-type connectors, null modem female-male RS232 cable (for the optional serial printer connection. The cable is included in optional printer package) Data exchange rate: up to 57.6 Kbaud for the field firmware upgrading and 19.2 Kbaud for test report printing on the optional s
13、erial printer Environmental Conditions Operating temperature range: -15 to 55 C (5 to 130F) Storage temperature range: -50 to 60 C (-60 to 140F) Relative humidity: to 90% noncondensing (operating) 95% noncondensing (storage) Physical Data Dimensions: (240 x 115 x 50 mm) (H x W x D) 9.5 x 4.5 x 1.9 i
14、n. Weight Test Set: 890 g (1.9 lbs.) with Leads 1.4 kg (3.1 lbs.) M AVTMTTR25 Rev C April 2008 38 Optional Accessories ? Battery/line-powered serial thermal printer package for 120 V ac (p/n 35755-1). The package includes the thermal printer, a battery pack, an AC adapter and an interface cable. ? B
15、attery/line-powered serial thermal printer package for 230 V ac (p/n 35755-2). The package includes the thermal printer, a battery pack, an AC adapter and interface cable. ? Test cable, 12 ft (3.6 m) for single phase transformer testing, shielded, heavy- duty clip-end terminated, (p/n 35942). The le
16、ads are marked according to ANSI, IEC, and Australian Standards. ? Additional printer paper, one roll, (p/n 26999) ? USB Serial Adapter (p/n 35871) for connecting a TTR25 RS232 port to a PC USB port. The adapter is used if a PC does not have an RS232 port. ? Battery Replacement (six required) p/n 35
17、956 AVTMTTR25 Rev C April 2008 39 Appendix B ORDERING INFORMATION VX represents rated voltage on the low-voltage winding. M AVTMTTR25 Rev C April 2008 42 T-Type Transformers T-type transformers represent a special type of three-phase transformers. This transformer may be tested as a single phase tra
18、nsformer. To make a measurement on a T-type transformer, the jumpers indicated in Table C-1 should be applied to the appropriate terminals of the T-type transformer. The TTR25 measured turns ratio should be compared to the calculated turns ratio indicated in Table C-1. Notes to Table C-1 1. Any conn
19、ection(s) to ground/case of T-type transformer on H or X side should be removed before testing a transformer. 2. Expect that polarity of the windings is normal (“+” sign is displayed in front of the turns ratio test result) Table C-1 ANSI Transformer Winding Phase Relationship Winding Connection Win
20、ding Tested IEC Vector Group High-Voltage Winding (H) Low-Voltage Winding (X) External Jumpers Phase tested High- Voltage Winding Low- Voltage Winding Calculated Turn Ratio T-T 0 X1 - H1 -H2 X1 -X2 A B H1 - H2 H1 H3 X1 - X2 X1 X3 X H V V X H V V T-T 30 lag H1 H2 -H3 X1 -X2 A B H1 H3 H2 H3 X1 - X2 X1
21、 X3 2 3 X H V V 3 2 X H V V T-T 30 lead H2 -H3 X1 X3 A B H1 H3 H2 H3 X1 X3 X2 X1 2 3 V V X H 3 2 X H V V Appendix C AVTMTTR25 Rev C April 2008 43 Notes to Table C-2 Transformer terminal markings for distribution and power transformers marked in accordance with requirements of American National Stand
22、ard Institute, Inc (ANSI) standard C57.12.70 1978. Definition of Symbol Designations H1, H2, H3 External terminals on HV transformer winding. X1, X2, X3 External terminals on LV transformer winding. H0 External neutral terminal on HV transformer winding. X0 External neutral terminal on LV transforme
23、r winding. * Inaccessible neutral point on HV or LV transformer winding. VH Nameplate voltage rating (line-to-line) of HV transformer winding. VX Nameplate voltage rating (line-to-line) of LV transformer winding. A, B, C Winding tested on HV side of transformer. a, b, c Winding tested on LV side of
24、transformer. M AVTMTTR25 Rev C April 2008 44 Table C-2 ANSI Transformer Winding Phase Relationship Copyright 1999 Megger Winding Connection Winding Tested Diag No. IEC Vector Group High-Voltage Winding (H) Low-Voltage Winding (X) Phase Tested Winding Shorted By TTR High- Voltage Winding Low- Voltage
25、 Winding Measured Turn Ratio 1 1 1ph0 1 H1 - H2 X1 - X2 V V H X 2 1 1ph6 1 H1 - H2 X2 - X1 V V H X 3 Dd0 A B C H1 - H3 H2 - H1 H3 - H2 X1 - X3 X2 - X1 X3 - X2 V V H X 4 Dd6 A B C H1 - H3 H2 - H1 H3 - H2 X3 - X1 X1 - X2 X2 - X3 V V H X 5 Dyn1 A B C H1 - H3 H2 - H1 H3 - H2 X1 - X0 X2 - X0 X3 - X0 V V
26、H X 3 6 Dyn7 A B C H1 - H3 H2 - H1 H3 - H2 X0 - X1 X0 - X2 X0 - X3 V V H X 3 7 YNyn0 A B C H1 - H0 H2 - H0 H3 - H0 X1 - X0 X2 - X0 X3 - X0 V V H X Appendix C AVTMTTR25 Rev C April 2008 45 Table C-2 ANSI Transformer Winding Phase Relationship Copyright 1999 Megger Winding Connection Winding Tested Di
27、ag No. IEC Vector Group High-Voltage Winding (H) Low-Voltage Winding (X) Phase Tested Winding Shorted By TTR High- Voltage Winding Low- Voltage Winding Measured Turn Ratio 8 YNyn6 A B C H1 - H0 H2 - H0 H3 - H0 X0 - X1 X0 - X2 X0 - X3 V V H X 9 YNd1 A B C H1 - H0 H2 - H0 H3 - H0 X1 - X2 X2 - X3 X3 -
28、X1 V V H X 3 10 YNd7 A B C H1 - H0 H2 - H0 H3 - H0 X2 - X1 X3 - X2 X1 - X3 V V H X 3 11 Dy1 A B C H3 - H2 H1 - H3 H2 - H1 H1-(H3-H2) H2-(H1-H3) H3-(H2-H1) X1 - X2 X2 - X3 X3 - X1 V V H X 3 12 Dyn5 A B C H1 - H3 H2 - H1 H3 - H2 X3 - X0 X1 - X0 X2 - X0 V V H X 3 13 Dy5 A B C H3 - H2 H1 H3 H2 H1 H1-( H
29、3-H2) H2-( H1-H3) H3-( H2-H1) X3 - X1 X1 - X2 X2 - X3 V V H X 3 M AVTMTTR25 Rev C April 2008 46 Table C-2 ANSI Transformer Winding Phase Relationship Copyright 1999 Megger Winding Connection Winding Tested Diag No. IEC Vector Group High-Voltage Winding (H) Low-Voltage Winding (X) Phase Tested Windin
30、g Shorted By TTR High- Voltage Winding Low- Voltage Winding Measured Turn Ratio 14 Dy7 A B C H3 - H2 H1 - H3 H2 - H1 H1-(H3-H2) H2-(H1-H3) H3-(H2-H1) X2 - X1 X3 - X2 X1 - X3 V V H X 3 15 Dyn11 A B C H1 - H3 H2 - H1 H3 - H2 X0 - X3 X0 - X1 X0 - X2 V V H X 3 16 Dy11 A B C H3 - H2 H1 - H3 H2 - H1 H1-(H
31、3-H2) H2-(H1-H3) H3-(H2-H1) X1 - X3 X2 - X1 X3 - X2 V V H X 3 17 Dz0 A B C H1 - H3 H2 - H1 H3 - H2 X1 - X3 X2 - X1 X3 - X2 V V H X 18 Dz6 A B C H1 - H3 H2 - H1 H3 - H2 X3 - X1 X1 - X2 X2 - X3 V V H X 19 YNy0 A B C H2 - H0 H3 - H0 H1 - H0 H1-(H2-H0) H2-(H3-H0) H3-(H1-H0) X1 - X3 X2 - X1 X3 - X2 V V H
32、 X Appendix C AVTMTTR25 Rev C April 2008 47 Table C-2 ANSI Transformer Winding Phase Relationship Copyright 1999 Megger Winding Connection Winding Tested Diag No. IEC Vector Group High-Voltage Winding (H) Low-Voltage Winding (X) Phase Tested Winding Shorted By TTR High- Voltage Winding Low- Voltage
33、Winding Measured Turn Ratio 20 Yyn0 A B C H1 - H3 H2 - H1 H3 - H2 X1 - X3 X2 - X1 X3 - X2 V V H X 21 Yy0 A B C H1 - H3 H2 - H1 H3 - H2 X1 - X3 X2 - X1 X3 - X2 V V H X 22 YNy6 A B C H2 - H0 H3 - H0 H1 - H0 H1-(H2-H0) H2-(H3-H0) H3-(H1-H0) X3 - X1 X1 - X2 X2 - X3 V V H X 23 Yyn6 A B C H1 - H3 H2 - H1
34、H3 - H2 X3 - X1 X1 - X2 X2 - X3 V V H X 24 Yy6 A B C H1 - H3 H2 - H1 H3 - H2 X3 - X1 X1 - X2 X2 - X3 V V H X 25 Yzn1 A B C H1 - H3 H2 - H1 H3 - H2 X1 - X0 X2 - X0 X3 - X0 V V H X 3 M AVTMTTR25 Rev C April 2008 48 Table C-2 ANSI Transformer Winding Phase Relationship Copyright 1999 Megger Winding Con
35、nection Winding Tested Diag No. IEC Vector Group High-Voltage Winding (H) Low-Voltage Winding (X) Phase Tested Winding Shorted By TTR High- Voltage Winding Low- Voltage Winding Measured Turn Ratio 26 Yz1 A B C H3 - H2 H1 - H3 H2 - H1 H1-(H3+H2) H2-(H1+H3) H3-(H2+H1) X1 - X2 X2 - X3 X3 - X1 V V H X 3
36、 2 27 Yzn5 A B C H1 - H3 H2 - H1 H3 - H2 X3 - X0 X1 - X0 X2 - X0 V V H X 3 28 Yz5 A B C H3 - H2 H1 - H3 H2 - H1 H1-(H3+H2) H2-(H1+H3) H3-(H2+H1) X3 - X1 X1 - X2 X2 - X3 V V H X 3 2 29 Yzn7 A B C H1 - H3 H2 - H1 H3 - H2 X0 - X1 X0 - X2 X0 - X3 V V H X 3 30 Yz7 A B C H3 - H2 H1 - H3 H2 - H1 H1-(H3+H2)
37、 H2-(H1+H3) H3-(H2+H1) X2 - X1 X3 - X2 X1 - X3 V V H X 3 2 Appendix C AVTMTTR25 Rev C April 2008 49 Table C-2 ANSI Transformer Winding Phase Relationship Copyright 1999 Megger Winding Connection Winding Tested Diag No. IEC Vector Group High-Voltage Winding (H) Low-Voltage Winding (X) Phase Tested Wi
38、nding Shorted By TTR High- Voltage Winding Low- Voltage Winding Measured Turn Ratio 31 Yzn11 A B C H1 - H3 H2 - H1 H3 - H2 X0 - X3 X0 - X1 X0 - X2 V V H X 3 32 Yz11 A B C H3 - H2 H1 - H3 H2 - H1 H1-(H3+H2) H2-(H1+H3) H3-(H2+H1) X1 - X3 X2 - X1 X3 - X2 V V H X 3 2 33 ZNy5 A B C H1 - H0 H2 - H0 H3 - H
39、0 X3 - X1 X1 - X2 X2 - X3 V V H X 3 34 Zy5 A B C H3 - H2 H1 - H3 H2 - H1 H1-(H3+H2) H2-(H1+H3) H3-(H2+H1) X3 - X1 X1 - X2 X2 - X3 V V H X 3 2 35 ZNy11 A B C H1 - H0 H2 - H0 H3 - H0 X1 - X3 X2 - X1 X3 - X2 V V H X 3 36 Zy11 A B C H3 - H2 H1 - H3 H2 - H1 H1-(H3+H2) H2-(H1+H3) H3-(H2+H1) X1 - X3 X2 - X1 X3 - X2 V V H X 3 2 M AVTMTTR25 Rev C April 2008 50 Table C-2 ANSI Transformer Winding Phase Relationship Copyright 1999 Megger Winding Connection Winding Tested Diag No. IEC Vector Group High-Voltage Winding (H) Low-Voltage Windi