1、5 and 15 kV DC Dielectric Test Sets Continuously variable test voltage Rugged field construction Compact and portable Order Online: www.BiddleM DESCRIPTION Dielectric test sets measure leakage current while applying a dc voltage at or above the insulation systems operating level. This measurement ai

2、ds in determining the insulation systems ability to withstand overvoltages such as lightning strikes and switching surges. APPLICATIONS Megger portable dc dielectric test sets check the electrical insulation quality of motors, power cables, switchgear, insulators, transformers and capacitors. Typica

3、l applications include acceptance and maintenance testing of critical equipment used by electrical utility substations and industrial plant distribution systems. Power apparatus manufacturers may also use the equipment to perform QA/QC production tests. The test sets can be used to perform step-volt

4、age and proof tests which, when incorporated into a routine maintenance program, can aid in predicting potential failure before breakdown occurs. Two models are available; a 5-kV unit for testing equipment rated 2.5 kV and below, and a 15-kV model for use on equipment rated 7.5 kV and below. Both ar

5、e suitable for testing power cable, switchgear and rotating machinery in accordance with IEEE, ICEA, NEMA and ANSI guidelines. Because Megger dc dielectric test sets act like full-wave rectified units, they also are suitable for applications involving vacuum bottles. DC vs AC High-Potential Testing

6、Direct current high-potential testing provides several advantages over alternating current. Direct current test equipment uses far less power, provides fast charging of highly capacitive test samples, can be easily transported to the test site and costs less. Additionally, the dc test can detect inc

7、ipient breakdown without the possibility of damage to good insulation. FEATURES AND BENEFITS Compact and portable Air insulated, uses no oil 2% accuracy Leakage current measurement as low as 0.1 mA Continuously variable test voltage with zero-start safety interlock Fast charging of high-capacitance

8、samples Current guard circuit for highly accurate measurements Strip chart recorder for hard copies (optionally available) Safety and Reliability Input and output line circuit breaker Output current overload relay Zero-start interlock for high-voltage output Pushbutton controls and indicating lights

9、 for high voltage ON/OFF Full circuit breaker protection Connection for external permissive and safety interlocks 15 kV model RadioFans.CN 收音机爱 好者资料库 5 and 15 kV DC Dielectric Test Sets SPECIFICATIONS Input 120 Vac, 50/60 Hz Output Cat. No. 220005 Voltage (maximum): 0 to 5 kVdc, negative with respec

10、t to ground Current (maximum): 5 mA continuous Metering Kilovoltmeter: 4-in. (102-mm) taut band with two ranges, 0 to 2.5 and 0 to 5 kV Current Meter: 4-in. (102-mm) taut band with four ranges, 0 to 5/50/500 A and 5 mA Cat. No. 220015 Voltage: 0 to 15 kVdc, negative with respect to ground Current: 2

11、 mA continuous Short Circuit: 12 mA max., limited by circuit breaker Metering Kilovoltmeter: 4-in. (102-mm) taut band with two ranges, 0 to 7.5 and 0 to 15.0 kV Current Meter: 4-in. (102-mm) taut band with four ranges, 0 to 5/50/500 A and 5 mA Accuracy 2% of full scale Temperature Range 0 to 122 F (

12、17.7 to +50 C) operating 5 kV model MeterCenter 2046 West Peninsula Circle - Chandler, AZ 85248 USA Tel +1 480-659-8351 Toll Free (800) 230-6008 Fax +1 480-659-8361 Email: SalesMeterC Websites: www.MeterC www.BiddleM Item (Qty)Cat. No. DC Dielectric Test Sets 5 kV220005 15 kV220015 Included Accessor

13、ies Ground connection cable, 10 ft 3 m4702 kV/M test record graph paper (100-sheet pad)220000 Power cord, Cat. No. 22001517032 ORDERING INFORMATION Megger ISO STATEMENT Registered to ISO 9001:1994 Reg no. Q 09250 Registered to ISO 14001 Reg no. EMS 61597 5_15KV_DCTS_DS_en_V01 www.MeterC Megger is a

14、registered trademark ItemCat. No. Optional Accessories Strip chart recorder220003 High-voltage resistance discharge stick222070-62 “The Lowdown on High-Voltage DC Testing”AVTM22P-1 9.4 H x 13.5 W x 10 D in. 24.8 H x 34.3 W x 25.4 D cm 12 H x 20.5 W x 13 D in. 30.5 H x 52 W x 33 D cm Model 5 kV 15 kV

15、 Test Voltage Range* 0 to 2.5 kVdc 0 to 5 kVdc 0 to 7.5 kVdc 0 to 15 kVdc Max. Power System Voltage 2.5 kVac (phase-to-phase) 7.5 kVac (phase-to-phase) Output Current (120-Vac input) 5 mA for 12 min; 2 mA continuous CAT. NO. 220005 220015 Dimensions 5 mA continuous * Negative polarity with respect to ground Weight 20.5 lb (9.3 kg) 35.2 lb (16 kg) RadioFans.CN 收音机爱 好者资料库